top of page
hujayasupply

1x RG11 + 3×2.5 Power Cable + 4x1x2x24AWG Data Pairs SWA LSZH Sheathed Composite Cable

Construction:

1x75Ohm RG11 Coaxial Cable ( in the center of the cable core) Conductor 1.63mm Solid bare copper Insulation Polyethylene. Diameter 7.25mm. Shield Braid of bare copper wire. Coverage 95% Sheath LSZH sheath. Nominal outer diameter is 10.3mm. Sheath Color Black

4x1x2x24AWG Shielded Twisted Pair data cable ( around coaxial cable) Conductor 7/0.2mm Stranded tinned copper. Insulation PVC material. Thickness 0.5mm. Insulation Color White and black Individual Shield Aluminum polyester tape Drain Wire 24 AWG stranded tinned copper Sheath LSZH sheath. Thickness 0.80mm. Sheath Color Black with white number code

3×2.5mm² Power Cable ( around coaxial cable) Conductor 2.5mm² Stranded tinned copper wire. Insulation XLPE. Outer diameter 3.41mm Insulation Color Blue, Brown and Green/Yellow

Element Assembly Filler PP material (around coaxial cable) Wrapping Tape Polyester tape or woven tape Inner Sheath Black LSZH, thickness 1.1mm Armor Steel wire armor, dia. 1.25mm Outer Sheath LSZH, thickness 1.8mm, nominal outer diameter 26.0±1.0mm Sheath Color Black Cable Weight 1100kg/km

Electrical and Physical Properties@20°C:

Coaxial Cable

Impedance: 75±3Ohm (@1MHz)

Max. Attenuation: 3.3dB/100m @50MHz

Power Cable

Electrical Resistance: 7.41Ohm/km

Insulation Resistance: ≥5500 MOhmxkm

Data Pairs

Electrical Resistance: 90Ohm/km

Insulation Resistance: ≥1000 MOhmxkm

Element Assembly

Conductor DC resistance per km@20°C:

24AWG: 95.8ohm/km

2.5mm²: 7.4ohm/km

1.63mm: 9.26ohm/km

Minimum Bending Radius: 312mm

Temperature Range: -10°C~70°C

Fire Performance:

Flame Propagation: IEC60332-1

Low Smoke Capacity: IEC61034-1/2

Halogen Free: IEC60754-1/2

1 view0 comments

Comments


bottom of page