When installing the battery charger as a replacement part, it is necessary to verify the proper charger settings and adjust as necessary.


1. Incoming AC voltage 115 or 230 volts.

2. Battery voltage - 12 or 24 volts DC.

3. Battery type - Lead Acid/Ni-Cad or 18 Cell / Ni-Cad 10 or 20 Cell.


If battery charger is powered with incorrect settings, damage to the charger and/or batteries may occur.


ree

The Firetrol Battery charge feature a fully automatic 4 Step charging cycle. The charging cycle are as indicate :

Step 1 : Qualification stage (Flashing yellow and green LED). During this stage, the battery charger checks the batteries to insure they can accept a fast charge. It also checks for missing or defective batteries. If the charger detect missing or defective batteries a fault will given (solid red LED).

Step 2 : Fast Charge (solid yellow LED). Charges the batteries until they reach peak voltage.

Step 3 : Bulk Charge (Solid yellow LED and slow blinking green LED). Charges the batteries at a constant potential of peak voltage until current reaches 500mA.

Step 4 : Float charge (Solid Green LED). Trickle charges the batteries to maintain peak potential.

The battery charger also includes the following :

- Selectable AC power voltage ( 115 or 230 V )

- Selectable battery voltage ( 2 or 24 V )

- Selectable battery type ( Lead acid, NiCad 9 or 18 cell, NiCad 10 or 20 cell )

- AC power fuse ( Type 3AG, 6A,250V )

- DC power fuse ( Type 3AB, 20A, 250V )

- Charger reset push - button (resets charging cycle to beginning )



ree


 
 
 

Recent Posts

See All
Siemens 7ML6003-1BC00-1AA3

Siemens 7ML6003-1BC00-1AA3 SITRANS LT500 universal level controller: continuous, non-contact, for liquids, slurries, and solids. Monitors...

 
 
 
Siemens 7ML6003-1AB00-1AA3

Siemens 7ML6003-1AB00-1AA3 SITRANS LT500 universal level controller: continuous, non-contact, for liquids, slurries, and solids. Monitors...

 
 
 
Siemens 7ML6003-1BC01-1AA3-Z E21

Siemens 7ML6003-1BC01-1AA3-Z E21 SITRANS LT500 universal level controller: continuous, non-contact, for liquids, slurries, and solids....

 
 
 

Comments


© 2023 Hujaya Supply. All rights reserved.

  • Facebook
  • Linkedin
bottom of page