When installing the battery charger as a replacement part, it is necessary to verify the proper charger

settings and adjust as necessary.

1. Incoming AC voltage 115 or 230 volts.

2. Battery voltage – 12 or 24 volts DC.

3. Battery type – Lead Acid / Ni-Cad 9 or 18 Cell / Ni-Cad 10 or 20 Cell.

If battery charger is powered with the incorrect settings, damage to the charger and/or batteries may occur.

The Firetrol® battery charger features a fully automatic 4 step charging cycle. The charging cycles are as

indicated:

Step 1: Qualification Stage (Flashing yellow and green LEDs)

            During this stage, the battery charger checks the batteries to insure they can accept a fast charge.

            It also checks for missing or defective batteries. If the charger detects missing or defective batteries

            a fault will be given (solid red LED).

Step 2: Fast Charge (Solid yellow LED)

           Charges the batteries until they reach peak voltage.

Step 3: Bulk Charge (Solid yellow LED and slow blinking green LED)

           Charges the batteries at a constant potential of peak voltage until current reaches 500mA.

Step 4: Float Charge (Solid green LED)

           Trickle charges the batteries to maintain peak potential.

• Charger reset push-button (resets charging cycle to beginning)